Permit: T16FO00073

Parcel: 125111530


Addresses:

3809 E 3RD ST


Inspection Status: Approved

Inspection History: FIRE INSP - STATE LICENSE

Permit Number - T16FO00073

Inspection Description - FIRE INSP - STATE LICENSE

Inspection Status - Approved

Date Description Inspector Results Comments
11/10/2016 FIRE INSP - STATE LICENSE Approved all violations have been abated
10/17/2016 FIRE INSP - STATE LICENSE Denied TFC 605.6 Unapproved Conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
1) You shall place an approved cover on the open ceiling outlet with capped wires in " F " Room.
TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring.
1) You shall remove extension cord in 'F' Room powering fish tank
2) You shall remove extension cord in 'F' Room powering CD player/ Halloween lights and phone charger.
TFC 907.3.4 Wiring. The wiring to the auxiliary devices and equipment used to accomplish fire safety functions shall be monitored for integrity in accordance with NFPA 72.
1) A lock out switch shall be placed on the #17 circuit labeled FA in refrigerator room.