Inspection Status: Approved
Inspection History: FIRE INSP - STATE LICENSE
Permit Number - T16FO00073
Inspection Description - FIRE INSP - STATE LICENSE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2016 | FIRE INSP - STATE LICENSE | Approved | all violations have been abated | |
| 10/17/2016 | FIRE INSP - STATE LICENSE | Denied | TFC 605.6 Unapproved Conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 1) You shall place an approved cover on the open ceiling outlet with capped wires in " F " Room. TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. 1) You shall remove extension cord in 'F' Room powering fish tank 2) You shall remove extension cord in 'F' Room powering CD player/ Halloween lights and phone charger. TFC 907.3.4 Wiring. The wiring to the auxiliary devices and equipment used to accomplish fire safety functions shall be monitored for integrity in accordance with NFPA 72. 1) A lock out switch shall be placed on the #17 circuit labeled FA in refrigerator room. |