Inspection History Details
Inspection Status: Denied
Inspection History: FIRE INSP - STATE LICENSE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2016 | FIRE INSP - STATE LICENSE | Denied | TFC 703.1 MAINTENANCE The required fire-resistance rating of fire resistance-rated-construction (including walls, fires tops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. 1) You shall seal around conduit in janitors closet with an approved fire rated sealant to match the fire resistivity of the rated ceiling. 5303.5.3 SECURING COMPRESSED GAS CONTAINERS, CYLINDERS AND TANKS. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1) You shall secure your Oxygen tanks from falling in your Oxygen storage room. |
|
| 10/12/2016 | FIRE INSP - STATE LICENSE | Approved | All violations have been ebated. |