Permit: T16FC00316

Parcel: 125115610


Addresses:

3630 E 3RD ST


Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Permit Number - T16FC00316

Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
12/30/2016 FIRE SPKLR - UG, PIPING, HYDRO Approved Changed out PVC to CPVC blazemaster pipe. Added thrust blocks. 200psi>2hrs
12/29/2016 FIRE SPKLR - UG, PIPING, HYDRO Denied DENIED
1) Still need thrust blocks.
2) Not pumped up. Still need hydro on 2".
Additional RI fee added. Need to pay before permit finaled.
12/27/2016 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval UG/Hydro approved for the 4" only.
1) replace 2" pvc with listed product.
2) add thrust blocks to change of directions
12/23/2016 FIRE SPKLR - UG, PIPING, HYDRO Denied Not ready.
1) need thrust blocks at each change of direction.
2) PVC pipe not listed for fire. Either provide cut sheets showing it's listed for fire or replace with a listed product.