Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
Permit Number - T16FC00316
Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/30/2016 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | Changed out PVC to CPVC blazemaster pipe. Added thrust blocks. 200psi>2hrs | |
12/29/2016 | FIRE SPKLR - UG, PIPING, HYDRO | Denied | DENIED 1) Still need thrust blocks. 2) Not pumped up. Still need hydro on 2". Additional RI fee added. Need to pay before permit finaled. |
|
12/27/2016 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | UG/Hydro approved for the 4" only. 1) replace 2" pvc with listed product. 2) add thrust blocks to change of directions |
|
12/23/2016 | FIRE SPKLR - UG, PIPING, HYDRO | Denied | Not ready. 1) need thrust blocks at each change of direction. 2) PVC pipe not listed for fire. Either provide cut sheets showing it's listed for fire or replace with a listed product. |