Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T16FC00313
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2017 | FIRE - ALARM FINAL | Approved | Fire sprinkler 46 seconds (Pass) Tested all smoke detectors, dampers, fire doors, manual pull stations, remote annunciator, primary power. Fire alarm is now approved and active. | |
| 09/11/2017 | FIRE - ALARM FINAL | Denied | Smoke detectors to close to the air vents move to greater than 3'. Smoke detector spacing in corridors needs to be adjusted to not exceed 30'. Smoke detecotrs need to be moved closer to the doors that they are closing. Replace the vestibule speaker strobe with a strobe only to stop the backfeed. Need to adjust the program (room number/names and descriptions) and re pretest the fire alarm prior to calling in fire final. Need to confirm the monitoring. Fire alarm system will need a intelligability and audibility test after occupancy. Could not test the water flow today. Ansul system tested. This is 1/2 of inspections. |