Inspection History Details
Inspection Status: Closed
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2022 | FIRE - ALARM FINAL | Closed | PERMIT CLOSED CONTRACTOR DID NOT CALL IN INSPECTION. SYSTEM NOT VERIFIED. | |
| 03/23/2017 | FIRE - ALARM FINAL | Partial Approval | provide the audibility and inteligability test per NFPA 72 and ROC 72 form. Program the voice system to also alarm in Spanish. | |
| 03/17/2017 | FIRE - ALARM FINAL | Partial Approval | 1) Need box around plug for communicator. 2) All games need to shut down on general alarm. Not just for suppression hood. All general alarms. All three hoods, smoke, pull, water flow. Relay for game shutdown malfunctioned (burned up) during testing. 3) Duct smokes not shutting down air handlers. 4) Need ROC/72 document. |