Inspection Status: Closed

Inspection History: FIRE - ALARM FINAL

Permit Number - T16FC00290

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Closed

Date Description Inspector Results Comments
10/13/2022 FIRE - ALARM FINAL Closed PERMIT CLOSED CONTRACTOR DID NOT CALL IN INSPECTION. SYSTEM NOT VERIFIED.
03/23/2017 FIRE - ALARM FINAL Partial Approval provide the audibility and inteligability test per NFPA 72 and ROC 72 form. Program the voice system to also alarm in Spanish.
03/17/2017 FIRE - ALARM FINAL Partial Approval 1) Need box around plug for communicator.
2) All games need to shut down on general alarm. Not just for suppression hood. All general alarms. All three hoods, smoke, pull, water flow. Relay for game shutdown malfunctioned (burned up) during testing.
3) Duct smokes not shutting down air handlers.
4) Need ROC/72 document.