Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T16FC00118
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2016 | FIRE SPKLR - FINAL | Approved | ||
| 11/04/2016 | FIRE SPKLR - FINAL | Denied | 1) bell not working. 2) still have deflectors which are too far below beams and too far below smooth ceilings. 1 1/4-1 3/4 below beams. 1 1/4 - 4" below smooth ceiling. 3) addtional reinspection fee added. needs to pay before full approval. |