Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T16FC00118
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2016 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
| 11/02/2016 | FIRE SPKLR - OH PIPING & HYDRO | Denied | Missing heads. Heads too far off wall. Deflectors too far below beams. FDC added. | |
| 10/28/2016 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1) Hydro approved for current pipe installed. May need to install more pipe. 2) Sprinkler heads too far from deck. Max 4" 3) Need to add FDC. 4) May need to add more heads to meet coverage. Current install is not approved. Needs to talk to designer. Approved plans do not show beams. 5) Deflectors need to be parallel to the angle of the deck. Currently none of the deflectors are angled appropriately. |