Permit: T16FC00101

Parcel: 12109290B


Addresses:

2221 N ROSEMONT BL

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
09/21/2022 FIRE - ALARM FINAL Approved Signed by CBasaldua on October 11th 2016
10/11/2016 FIRE - ALARM FINAL Partial Approval Partial approval:



Simplex to provide NFPA 72 Record of completion, NFPA 72 Inspection Report. Simplex to submit As Built Drawings to TFD regarding the deleted items and other modifications.
10/10/2016 FIRE - ALARM FINAL Denied 1. Need to replace Potter tamper switch with monitor module.
2. Need to show as builds.
3. Need to test horn/strobes again.