Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T16FC00047
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2017 | FIRE - ALARM FINAL | Approved | ||
12/16/2016 | FIRE - ALARM FINAL | Partial Approval | Everything approved. Waiting on Dio from Simplex to add suite # to bldg address at the central station. | |
12/09/2016 | FIRE - ALARM FINAL | Denied | Did not test anything. Still needs full acceptance test. 1) Needs monitoring. 2) Remote annunciator not working. 3) Alarm shall activate upon waterflow. Currently, only the other suites alarm will activate upon waterflow. This alarm has not been wired to the waterflow switch. |