Case: T16DV04322

Parcel: 137302650

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
07/13/2016 INSP - INITIAL CODE ENFORCMENT Approved The owner called that someone will be home and made arrangements with the tenant on the bottom unit to check the toilet. Took Inspector Bigman to assist on the flushing of the toilet. The toilet was flused several times and the water was leaking to the bottom unit around the pipe of the toilet and the water was following the floor joist. It appears that the wax bowl ring is leaking. Did look at the toilet install and has ceramic tile butted to the toilet. That's the concern that the owner had and the grout needs to be removed in order to have the toilet removed. The owner needs to call a plumber to make the repairs. Will let the tenant know to wait on the repairs until the toilet is repaired upstairs. Will do N.O.V. RV.
07/12/2016 INSP - INITIAL CODE ENFORCMENT Approved Was called to the bottom unit and the hall bathroom is leaking water from the ceiling. A hole has been cut in the drywall and show signs of water leaking on the ABS piping for the toilet. Did check and no one home and left a card on the metal secuity door for the owner to call. RV.