Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2016 | INSP - FOLLOW UP CODE ENFORCE | Approved | PERMIT T16CM02491 FINAL CLOSE CASE | |
| 04/14/2016 | INSP - FOLLOW UP CODE ENFORCE | Approved | PERMIT T16CM02491 ISSUED FOR ELECTRICAL REPR, REPL WATER HEATER T16DV01145 | |
| 03/07/2016 | INSP - FOLLOW UP CODE ENFORCE | Approved | ONSITE INSPECTION THE TENANT IS MOVING OUT. THERE IS A NEW ELECTRIC WATER HEATER. THIS UNIT WAS INSTALLED WITHOUT A PERMIT IN AN UNSAFE MANNER. THE ORIGINAL UNIT WAS GAS FIRED. THERE IS 12 GAUGE NON SHEATHED METALLIC CABLE WHICH WAS CONNECTED TO A 50 AMP CIRCUIT BREAKER IN THE INTERIOR PANEL OF THE TRAILER. THERE ARE MULTIPLE CONDUCTORS ON ONE TERMINAL LUG. NEW ELECTRICAL CIRCUITS HAVE BEEN INSTALLED THAT ARE NOT COMPLIANT WITH CURRENT APPLICABLE CODES. THE INTERIOR PANEL IS NOT RATED FOR THE CURRENT USE. THERE ARE UNUSED OPENINGS IN THE INTERIOR PANEL. THE BEDROOM RECEPTACLE IS UNSERVICEABLE WITH BURNT MARKS. THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON THE INTERIOR PANEL. THERE ARE UNAPPROVED WIRING METHODS IN THE TRAILER. THE POWER HAS BEEN SHUT OFF AT THE PEDESTAL. |