Case: T16DV00010

Parcel: 123111390


Addresses:

1420 E WAVERLY ST


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T16DV00010

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
01/25/2016 INSP - INITIAL CODE ENFORCMENT Approved Inspection of main and rear unit at request of both tenants. Multiple violations and issues were found at location including, but not limited to: unit #2 including electrical, plumbing, lack of operable mechanical heat, lack of permit, inoperable bathroom window, inoperable doors; unit 1: unlockable bathroom window, gap between floor/wall in living room, screen door in disrepair. Main 60 amp service panels for both units have been modified; double lugging, added circuits, replaced circuit spanning across to carport does not meet code, has exposed conductors and are not rated for use in exterior environment. Wall heater in unit #2 has been tagged off by SWG for leak at pilot. Exterior water services lines modified and replaced with PEX5006, which is not rated for UV exposure, no permit on file. Smoke alarm in unit #2 lacks battery. Photos in Sire, detail on NOV.