Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T16DV00010
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2016 | INSP - INITIAL CODE ENFORCMENT | Approved | Inspection of main and rear unit at request of both tenants. Multiple violations and issues were found at location including, but not limited to: unit #2 including electrical, plumbing, lack of operable mechanical heat, lack of permit, inoperable bathroom window, inoperable doors; unit 1: unlockable bathroom window, gap between floor/wall in living room, screen door in disrepair. Main 60 amp service panels for both units have been modified; double lugging, added circuits, replaced circuit spanning across to carport does not meet code, has exposed conductors and are not rated for use in exterior environment. Wall heater in unit #2 has been tagged off by SWG for leak at pilot. Exterior water services lines modified and replaced with PEX5006, which is not rated for UV exposure, no permit on file. Smoke alarm in unit #2 lacks battery. Photos in Sire, detail on NOV. |