Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T16CM09706

Parcel: 136340830


Addresses:

7688 E KEITH DR

Inspection Status: Passed

Inspection History: RSEL - Electrical Progress

Date Description Inspector Results Comments
11/01/2018 RSEL - Electrical Progress BJONES Approved Entered by CBELL1 -
08/08/2018 RSEL - Electrical Progress GWest Denied Entered by GWEST2 - IC rated cans for bath ceiling or whereve insulation will be installed. Shower, approved shower ceiling cans only and GFCI protection at cans in shower stall. Subpanel required for Garage or a 3 line engineered and approved drawing for a non standard custom design of J-Box and feeders to garage.