Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2017 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 05/24/2017 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | 1-provide 2 points of attachment to bldg 2-provide bonding to gas and water 3-guyed wires required if mast is 36" above roof |