Permit: T16CM09487

Parcel: 137314780


Addresses:

5165 S RIVER RUN DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/22/2017 ELECTRIC - FINAL Approved
05/19/2017 ELECTRIC - FINAL Cancelled IVRS - RI canceled
04/24/2017 ELECTRIC - FINAL Denied MISSING POST TENSION TAG ON WATER MAIN.
PANEL BOX HAS TWO DRYER CIRCUITS, NONE FOR A/C
REAR RECEPTACLE NEAR HOSE BIB IN NOT A GFCI
RECEPTACLES IN FRONT BEDROOM ARE WIRED INCORRECTLY
SECURE OUTLETS AT KITCHEN COUNTER
SECURE DISHWASHER HOSE AS HIGH AS POSSIBLE UNDER SINK.
SITE SEWER AND PRE SLAB INSPECTIONS ARE STILL OPEN.
STOP INSPECTION