Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2017 | BUILDING - FINAL | Approved | ||
| 05/24/2017 | BUILDING - FINAL | Not ready for Inspection | CANCELED | |
| 05/22/2017 | BUILDING - FINAL | Partial Approval | ALL PRIOR INSPECTION ITEMS HAVE BEEN CORRECTED. NOW JUST WAITING FOR REQUIRED CERTIFICATES. | |
| 05/19/2017 | BUILDING - FINAL | Cancelled | IVRS - RI canceled | |
| 04/24/2017 | BUILDING - FINAL | Denied | MISSING POST TENSION TAG ON WATER MAIN. PANEL BOX HAS TWO DRYER CIRCUITS, NONE FOR A/C REAR RECEPTACLE NEAR HOSE BIB IN NOT A GFCI RECEPTACLES IN FRONT BEDROOM ARE WIRED INCORRECTLY SECURE OUTLETS AT KITCHEN COUNTER SECURE DISHWASHER HOSE AS HIGH AS POSSIBLE UNDER SINK. SITE SEWER AND PRE SLAB INSPECTIONS ARE STILL OPEN. STOP INSPECTION |