Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T16CM09487

Parcel: 137314780


Addresses:

5165 S RIVER RUN DR

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
07/12/2017 BUILDING - FINAL Approved
05/24/2017 BUILDING - FINAL Not ready for Inspection CANCELED
05/22/2017 BUILDING - FINAL Partial Approval ALL PRIOR INSPECTION ITEMS HAVE BEEN CORRECTED. NOW JUST WAITING FOR REQUIRED CERTIFICATES.
05/19/2017 BUILDING - FINAL Cancelled IVRS - RI canceled
04/24/2017 BUILDING - FINAL Denied MISSING POST TENSION TAG ON WATER MAIN.
PANEL BOX HAS TWO DRYER CIRCUITS, NONE FOR A/C
REAR RECEPTACLE NEAR HOSE BIB IN NOT A GFCI
RECEPTACLES IN FRONT BEDROOM ARE WIRED INCORRECTLY
SECURE OUTLETS AT KITCHEN COUNTER
SECURE DISHWASHER HOSE AS HIGH AS POSSIBLE UNDER SINK.
SITE SEWER AND PRE SLAB INSPECTIONS ARE STILL OPEN.
STOP INSPECTION