Permit: T16CM09274

Parcel: 137051060


Addresses:

5017 S 12TH AV


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T16CM09274

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2017 PLUMBING - GAS PRESSURE TEST Approved
02/15/2017 PLUMBING - GAS PRESSURE TEST Denied GUAGE READS ZERO
NO PAPERWORK FOUND
12/23/2016 PLUMBING - GAS PRESSURE TEST Denied 1-all underground fittings are to be coated per IPC, 20 mil. with adhesive
2-all tool marks to be coated
3-black pipe to be 6" above grade
4-pipe to be min. 12" below grade
5-provide approved bond clamp
6-water heater flue not properly terminated
12/22/2016 PLUMBING - GAS PRESSURE TEST Denied POST ADDRESS
NO PAPERWORK FOUND
NO ANSWER FRONT DOOR
RECALL
12/21/2016 PLUMBING - GAS PRESSURE TEST Denied NO PAPERWORK FOUND
NEXT DENIAL MAY RESULT IN A REFEE
12/19/2016 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*