Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T16CM09237

Parcel: 133231390

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/25/2017 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/13/2017 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1- SHALL PROVIDE AN APPROVED GROMET OR CHASE NIPPLE ON THE BACK TO BACK METAL BOXES. REFERENCE SECTION 250.148 A,B,C. 2011 NEC.