Permit: T16CM09120

Parcel: 110082380

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
12/22/2016 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
12/20/2016 PLUMBING - ROUGH, SOIL Denied 1- SHALL PROVIDE A SEPERATE 2" DRAIN FOR THE LAVATORY IN THE POWDER ROOM.
2- PROVIDE A WATER TEST ON THE SYSTEM.
12/12/2016 PLUMBING - ROUGH, SOIL Partial Approval 1- DWV WATER TEST PROVIDED.
2- THIS INSPECTION IS FOR THE UNDERSLAB ROUGH PLUMBING EXCEPT THE POWDER ROOM.
3- OKAY TO BACKFILL TRENCH EXCEPT AT POWDER ROOM.
12/09/2016 PLUMBING - ROUGH, SOIL Denied 1- DWV WATER TEST FOR THE WEST SIDE ROUGH PLUMBING WAS DOWN.
2- THE TRAP ARM FOR THE MASTER BEDROOM TUB REQUIRES A MINIMUM OF TWO TIMES THE PIPE DIAMETER TO AVOID HAVING A S TRAP.
3- SHALL CONNECT THE 2" WASTE LINE FOR THE WASHER BOX DOWNSTREAM OF THE WATER CLOSET.
4- RE TEST THE SYSTEM.