Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T16CM09039
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/26/2017 | FIRE - FINAL | Approved | ||
04/28/2017 | FIRE - FINAL | Denied | Still needs a sprink final. MC fire contacted, needs the following: 1) Submit new drawings showing actual layout on bottom floor. Will now be a small retail store. 2) Needs to address the obstruction (soffit) on south wall towards fire sprink monitoring panel. same notes in T16BU00529 |
|
04/03/2017 | FIRE - FINAL | Denied | The Sprinkler System that was installed ( permit # T16CM09039 ) never received an approval at final and the permit expired. The sprinkler system has never been serviced/inspected since it was installed, per the owner. This system is designed to 13-D for the top residential floors and 13 system for bottom floor that was supposed to become a restaurant. The bottom floor has sat vacant and the owner decided to change the planned use from a restuarant to a gift store. It is now under TI for the gift store on this permit and was seeking a fire final. No Fire Final shall be given until the fire sprinkler system passes a fire sprinkler final per its design, which means the permit must be re opened or a new permit must be applied for. The alarm/monitoring system for this sprinkler was approved under permit number T16FC00319. |