Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T16CM08976
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/22/2018 | FIRE - ALARM FINAL | Approved | ||
06/21/2018 | FIRE - ALARM FINAL | Denied | Alarm is not yet tied into Building 5. | |
06/20/2018 | FIRE - ALARM FINAL | Denied | * Alarm company or responsible party thereof shall be made available to test the alarm system for the 5000 numbered units. Party shall be knowledgeable in such functions to test alarm. * All tape and other objects shall be removed from sprinkler heads prior to next inspection. * 5102 shall have painted sprinkler head changed located in heater closet. * 5101 Light fixture shall be at least 4 inches from sprinkler head. * 5104 eschucheon missing. Attic cover missing. * 5106 ceiling cover not in place for either vent or fan. |