Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2018 | FIRE SPKLR - FINAL | Approved | per CB | |
| 06/20/2018 | FIRE SPKLR - FINAL | Denied | * Alarm company or responsible party thereof shall be made available to test the alarm system for the 5000 numbered units. Party shall be knowledgeable in such functions to test alarm. * All tape and other objects shall be removed from sprinkler heads prior to next inspection. * 5102 shall have painted sprinkler head changed located in heater closet. * 5101 Light fixture shall be at least 4 inches from sprinkler head. * 5104 eschucheon missing. Attic cover missing. * 5106 ceiling cover not in place for either vent or fan. |