Permit: T16CM08976

Parcel: 10712170F

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T16CM08976

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/22/2018 FIRE SPKLR - FINAL Approved per CB
06/20/2018 FIRE SPKLR - FINAL Denied * Alarm company or responsible party thereof shall be made available to test the alarm system for the 5000 numbered units. Party shall be knowledgeable in such functions to test alarm.
* All tape and other objects shall be removed from sprinkler heads prior to next inspection.
* 5102 shall have painted sprinkler head changed located in heater closet.
* 5101 Light fixture shall be at least 4 inches from sprinkler head.
* 5104 eschucheon missing. Attic cover missing.
* 5106 ceiling cover not in place for either vent or fan.