Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2017 | PLUMBING - INTERMEDIATE | Approved | ||
| 03/23/2017 | PLUMBING - INTERMEDIATE | Denied | 1- NOT READY FOR INSPECTION. | |
| 03/22/2017 | PLUMBING - INTERMEDIATE | Denied | 1- WATER SUPPLY TO THE WATER HEATER IS NOT THE SIZE THAT THE APPROVED PLANS CALL OUT. REFERENCE THE WATER5 DISTRIBUTION ISOMETRIC DRAWING. 2-SHALL PROVIDE HANGERS FOR THE HORIZONTAL VENTS ABOVE THE RESTROOMS EVERY 4'-0". 3- ELECTRIC AND PLUMBING IN WALLS IS OKAY |
|
| 03/21/2017 | PLUMBING - INTERMEDIATE | Not ready for Inspection |