Permit: T16CM08663

Parcel: 13321075A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T16CM08663

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2017 PLUMBING - INTERMEDIATE Approved
03/23/2017 PLUMBING - INTERMEDIATE Denied 1- NOT READY FOR INSPECTION.
03/22/2017 PLUMBING - INTERMEDIATE Denied 1- WATER SUPPLY TO THE WATER HEATER IS NOT THE SIZE THAT THE APPROVED PLANS CALL OUT. REFERENCE THE WATER5 DISTRIBUTION ISOMETRIC DRAWING.
2-SHALL PROVIDE HANGERS FOR THE HORIZONTAL VENTS ABOVE THE RESTROOMS EVERY 4'-0".
3- ELECTRIC AND PLUMBING IN WALLS IS OKAY
03/21/2017 PLUMBING - INTERMEDIATE Not ready for Inspection