Permit: T16CM08663

Parcel: 13321075A

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T16CM08663

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2017 BUILDING - FINAL Approved
05/15/2017 BUILDING - FINAL Denied 1- SEE NOTE # 5 AND THE DOMWSTIC WATER ISOMETRIC DRAWING SHOWING THE CIRCUIT SETTERS (BALANCE VALVES) CONTROL VALVES AND CHECK VALVE.
2- I SPOKE WITH THE G.C. AND PLBG. CONTRACTOR AND THEY STATED THAT THEY WILL PROVIDE A SEALED LETTER FROM THE MECHANICAL ENGINEER THAT HE WILL ACCEPT THE HOT WATER RETURN SYSTEM THAT WAS INSTALLED NOT AS PER THE APPROVED PLANS.
05/12/2017 BUILDING - FINAL Not ready for Inspection
05/11/2017 BUILDING - FINAL Denied 1- ACCESSIBLE WATER CLOSET SIDE WALL CLEARANCE SHALL BE WITHIN 16" TO 18" TO THE CENTER OF THE WATER CLOSET MAX.
2- SHALL PROVIDE HAMMER ARRESTORS FOR THE A.W.
3- SHALL CAULK THE DRINKING FOUNTAIN AND MOP SINK.
4- SHALL CONNECT THE THE ELECTRIC CONDUCTORS TO THE WATER HEATER.
5- SHALL INSTALL THE RECIRCULATION PUMP AS PER THE APPROVED DRAWINGS AND SECURE THE EXPANSION TANK.
6- SEE NOTES 3, & 4.
7 SHALL INSTALL GRAB BARS AS PER THE ANSI STANDARDS.
8- SHALL LOCATE THE ACCESSIBLE LAVATORY RIM 34" A.F.F MAX.
9 SHALL LOCATE OR PROVIDE THE TRAP PRIMERS FOR THE FLOOR DRAINS IN THE RESTROOMS.
05/08/2017 BUILDING - FINAL Denied 1- PLUMBING IS INCOMPLETE.
2- H.C. WATER CLOSET FLUSH HANDLES SHALL BE LOCATED ON THE OPEN SIDE OF ROOM.
3- ELECTRICAL RECEPTICALS AT THE LOUNGE SINK COUNTERTOP ARE LOOSE.
4- H.C. WATER CLOSETS REQUIRE OPEN FRONT SEATS.
5- INSPECTION STOP. THIS IS NOT A COMPLETE INSPECTION.