Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2017 | ELECTRIC - FINAL | Approved | APPROVED | |
| 01/06/2017 | ELECTRIC - FINAL | Denied | MISSING BOND BUSHING ON LOWER SOLAR CONDUIT MISSING WIRE CLAMP ON GEC AT SERVICE PANEL NEW SERVICE PANEL IS NOW A MAIN PANEL, NEUTRAL AND GROUND MUST BE BONDED TOGETHER. OLD SERVICE PANEL IN HOME IS NOW A SUB-PANEL, UN-BOND NEUTRAL AND GROUND. |
|
| 01/03/2017 | ELECTRIC - FINAL | Denied | MISSING GROUND ROD MISSING BOND BUSHING ON LOWER CONDUIT #3/0 NEUTRAL WIRE IS NOT LANDED PLASTIC AT THE BREAKER LUG IS BROKEN. END INSPECTION |
|
| 12/30/2016 | ELECTRIC - FINAL | Not ready for Inspection |