Permit: T16CM08597

Parcel: 110052240

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/28/2016 PLUMBING - FINAL Approved APPROVED
11/23/2016 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999

1- SHALL PROVIDE A MINIMUM OF 10 X 10 AIR VENTS LOCATED WITHIN 12" DOWN FROM CEILING AND 12" ABOVE THE PLATFORM FOR COMBUTION AIR.

2- SHALL PROVIDE GAS LINE BOND.

3- SHALL EXTEND THE FURNACE AND WATER HEATER FLU VENT 3' 0" ABOVE THE COOLER.

4- SHALL TIGHTEN UP THE UNISTRAP CLAMPS AT THE GAS LINE DROP TO METER.

5- SHALL PROVIDE A CARBON MONOXIDE DETECTOR.


*