Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2017 | BUILDING - FINAL | Approved | ||
| 05/05/2017 | BUILDING - FINAL | Partial Approval | PROVIDE A SEDIMENT TRAP AT FURNACE.GAS FLEX CANNOT EXCEED 3" AT FURNACE. A/C ON ROOF IS OVERFUSED. PROVIDE A BUSHING IN A/C DISCONNECT. DO NOT USE WHITE WIRE FOR POWER AT A/C UNIT. PROVIDE A ROOF JACK AT CONDENSATE DRAIN. PROVIDE 2" DUCT LINER IN EXPOSED DUCT ON ROOF. |