Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2017 | ELECTRIC - FINAL | Approved | ||
| 09/07/2017 | ELECTRIC - FINAL | Denied | STOOP EXIT DOORS EXTERIOR LIGHT FIXTURES TO BE SHIELDED HAMMER ARRESTORS LAUNDRY ARC FAULT CIRCUITS SEAL WATER CLOSET AT BASE PAINT CONDENSATE LINE |
|
| 06/29/2017 | ELECTRIC - FINAL | Not ready for Inspection | 2065 APPROVED ON 4/4 NO POWER AT THIS TIME OWNER NEEDS TO CONTACT TEP |
|
| 06/28/2017 | ELECTRIC - FINAL | Not ready for Inspection | called for elec. connect, deadfront missing from main service panel, romex in walls exposed in shed, address label needed at panel |