Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T16CM08564
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/26/2018 | FIRE - FINAL | Approved | Gate does not fail in the open position. Per Chief Carsten we are going to allow this for the protection of the animals. Gate will need to be maintained with the battery back up at all times. Fire service contracts are in place. Approval for C of O. | |
03/22/2018 | FIRE - FINAL | Partial Approval | 1. Insulation added to 1" lines. 2. 1" clearance added to sprinkler head deflectors. 3. Still need to address the gate and contracts. |
|
03/05/2018 | FIRE - FINAL | Partial Approval | OK FOR TCO to occupy Need a site plan showing building numbers and FDC locations Gate needs to fail in the open position Add 1 weatherproof strobe to the walk in cooler remove the small wires from the fire sprinkler system relocate/add 3 heads Insulate the 1" pipe that is located outside |
|
03/01/2018 | FIRE - FINAL | Denied | Need to correct the emergency lights Need all gates and panic hardware to be in place Fire sprinkler needs a final KNOX switch for the gate is required FDC signs Pay-reinsoection fee |