Permit: T16CM08503

Parcel: 138144520

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T16CM08503

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2016 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/10/2016 ELECTRIC - FINAL Partial Approval OMIT OR PROTECT WIRING IN MECHANICAL ROOM FROM PHYSICAL DAMAGE
PROVIDE BUSHING AT A/C DISCONNECT
PROTECT CONDENSOR WIRINGF ROM PHYSICAL DAMAGE
UNDERSIZED WIRING TO 30 AMP DISCONNECT UNIT #123