Permit: T16CM08408

Parcel: 137060460


Addresses:

409 W DAKOTA ST

Inspection Status: Denied

Inspection History: ELECTRIC - CONSTRUCTION POWER

Date Description Inspector Results Comments
08/02/2019 ELECTRIC - CONSTRUCTION POWER Denied 1- Shall provide the approved acorn Ufer ground clamps.
2- Shall secure the Ufer ground conductor to the service pole.
08/02/2019 ELECTRIC - CONSTRUCTION POWER Approved Clear electric incr
07/31/2019 ELECTRIC - CONSTRUCTION POWER Partial Approval OK to clear electric TMPP. Add one additional ground rod 6 foot from first one. Add blank covers so there are no holes into the dead front. Add address label to panel. Exterior receptacle needs to be a GFCI.