Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2017 | PLUMBING - INTERMEDIATE | Approved | ||
| 02/08/2017 | PLUMBING - INTERMEDIATE | Not ready for Inspection | dwv not under test | |
| 02/07/2017 | PLUMBING - INTERMEDIATE | Denied | Correct horizontal dry vent below fixture flood level; each dry vent shall rise vertically to 6 inches above flood level. P3104.4 Secure pex into wall and overhead. |
|
| 02/06/2017 | PLUMBING - INTERMEDIATE | Denied | closet venting |