Permit: T16CM08163

Parcel: 140231920

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
11/01/2016 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
10/28/2016 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999


*
10/28/2016 ELECTRIC - RECONNECT Denied WATER HEATER TPV IS MISSING PIPE
NO PAN UNDER WATER HEATER
WIRE CONNECTOR IS MISSING AT WATER HEATER
10 GAUGE WIRE IN METAL CONDUIT WITHOUT PLASTIC BUSHINGS
DEAD FRONT MISSING AT HVAC DISCONNECT
BROKEN BREAKER IN SERVICE PANEL
NO SMOKE DETECTORS IN BEDROOMS OR HALLWAY.