Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2017 | FIRE - FINAL | Approved | ||
| 02/27/2017 | FIRE - FINAL | Partial Approval | Need to remove the watermotor gong. Add red tape around the 3' area from FACP and electrical panels. | |
| 02/22/2017 | FIRE - FINAL | Partial Approval | 1) Some exit signs and EM lights did not work. 2) Add FACP sign to door. 3) Need alarm final. |
|
| 01/05/2017 | FIRE - FINAL | Partial Approval | 1) TI on kitchen approved. 2) Need to research T15CM03554 before this permit is finaled. That permit is still open with fire violations however a COFO was approved. All items noted on the permit need to be resolved. 3) Cutler has submitted plans for sprinkler work. 4) Sprinkler system shall be monitored. 5) Additional repair items below: -Data room, hole in ceiling. -extinguishers need to be mounted and inspected/tagged. -add riser room sign to interior door. -add FACP sign to interior door that gets the sprink monitoring panel. Dan is general contractor 907-6638 |