Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T16CM07932

Parcel: 125030350


Addresses:

2927 E 3RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/08/2019 ELECTRIC - FINAL Approved
12/27/2018 ELECTRIC - FINAL Correction Required Drive Ground Rod at service so it will be covered by dirt when complete.
Secure the GEC and Water Bond to the wall.
Where is the Gas Bond locates, need to see for inspection.
Label all Circuit Breakers as required.
Water tight approved allweather cover required at the GFCI below the service panel.
Check/Tighten all GEC and Bonding Accorns and clamp