Permit: T16CM07849

Parcel: 122150890


Addresses:

3115 E LESTER ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
05/09/2017 PLUMBING - ROUGH, SOIL Approved
04/07/2017 PLUMBING - ROUGH, SOIL Denied 1- SHALL PROVIDE A WATER TEST ON THE DWV SYSTEM TO THE TOP OF VENTS THRU ROOF.
04/05/2017 PLUMBING - ROUGH, SOIL Denied 1- SHALL PROVIDE A WATER TEST ON DWV SYSTEM TO THE TOP OF THE VENTS THRU ROOF.
2- SHALL PROVIDE THE REQUIRED NAIL PLATES FOR THE TOP AND SOLE PLATES WHERE THERE IS PLUMBING RISERS AND WATER LINES.
3-SHALL PROVIDE 2" VENT THRU THE ROOF FOR THE WATER CLOSET VENT AS PER THE APPROVED PLAN.
4-SHALL PROVIDE (3) SIDED BLOCKING AT ALL A.C. SUPPLY VENTS.
5- SHALL SEAL ALL TOP PLATE PENETRATIONS WITH FIRE RATED FOAM OR CAULK.
6- SHALL PROVIDE A SWEEP 90 ON THE LAVATORY TRAP ARM. VENT 90 IS NOT APPROVED FOR DRAINAGE.