Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2017 | PLUMBING - ROUGH, SOIL | Approved | ||
| 04/07/2017 | PLUMBING - ROUGH, SOIL | Denied | 1- SHALL PROVIDE A WATER TEST ON THE DWV SYSTEM TO THE TOP OF VENTS THRU ROOF. | |
| 04/05/2017 | PLUMBING - ROUGH, SOIL | Denied | 1- SHALL PROVIDE A WATER TEST ON DWV SYSTEM TO THE TOP OF THE VENTS THRU ROOF. 2- SHALL PROVIDE THE REQUIRED NAIL PLATES FOR THE TOP AND SOLE PLATES WHERE THERE IS PLUMBING RISERS AND WATER LINES. 3-SHALL PROVIDE 2" VENT THRU THE ROOF FOR THE WATER CLOSET VENT AS PER THE APPROVED PLAN. 4-SHALL PROVIDE (3) SIDED BLOCKING AT ALL A.C. SUPPLY VENTS. 5- SHALL SEAL ALL TOP PLATE PENETRATIONS WITH FIRE RATED FOAM OR CAULK. 6- SHALL PROVIDE A SWEEP 90 ON THE LAVATORY TRAP ARM. VENT 90 IS NOT APPROVED FOR DRAINAGE. |