Inspection History Details
Inspection Status: Approved
Inspection History: ENGINEERING - FINAL
Permit Number - T16CM07762
Inspection Description - ENGINEERING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/29/2017 | ENGINEERING - FINAL | Approved | ||
09/13/2017 | ENGINEERING - FINAL | Partial Approval | 1) COMPLETE LANDSCAPING PER APPROVED PLANS 2) PROVIDE A CERT STATEMENT FROM THE ENG OF RECORD 3) SIDE WALK ALONG THE NE SIDE OF BLDG, RUN SLOPE DOES NOT MEET WHATS SHOWN ON APPROVED. SIDE WALK IS AT 7.6% AND SLOPE ON PLANS SHOWS 4.6%. 4) SIDEWALK SCUPPERS HAVE BEEN ADDED IN AREAS AND TAKEN AWAY IN OTHER AREAS, NOT PER PLAN. 5) PROVIDE A PLANS THAT SHOWS CHANGES MADE, OR BUILD SITE PER THE APPROVED PLANS |
|
09/11/2017 | ENGINEERING - FINAL | Not ready for Inspection | ||
09/05/2017 | ENGINEERING - FINAL | Not ready for Inspection | THE SITE IS NOT READY AT THIS TIME, THERE IS TO MUCH OF THE WORKING HAPPENING ADJACENT TO THE PEDESTRIAN PATHWAYS. 1) COMPLETE ALL OF THE EXTERIOR WORK ON THIS SITE OR FENCE THE WORK AREAS OFF FROM THE GENERAL PUBLIC, PROVIDE AS-BUILT/REVISED DRAWINGS THAT HAVE BEEN CHANGED ON THIS SITE. 2) THE TWO SOUTHERN MOST HANDICAP PARKING SPACES AND ACCESS AISLE ARE OVER THE MAXIMUM 2% RUNNING SLOPES AND WILL NEED TO BE CORRECTED PRIOR TO CALLING IN FOR ANOTHER FINAL ENGINEERING INSPECTION. |