Permit: T16CM07762

Parcel: 11101035C


Addresses:

3718 E RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T16CM07762

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/05/2017 ELECTRIC - INTERMEDIATE Approved
06/30/2017 ELECTRIC - INTERMEDIATE Partial Approval 1- 2ND FLOOR IS OKAY FOR ONE SIDE OF WALLS TO BE SHEET ROCKED.
05/23/2017 ELECTRIC - INTERMEDIATE Partial Approval ELECTRIC MC CONDUCTORS AND METAL BOXES ARE OKAY IN FIRST FLOOR WEST WING.
05/15/2017 ELECTRIC - INTERMEDIATE Partial Approval 1- ELECTRICAL INTERMEDIATE CORRECTIONS HAVE BEEN MADE FOR 1ST FLOO EAST WING ONLY.
05/05/2017 ELECTRIC - INTERMEDIATE Denied 1- SHALL PROVIDE GROUND SCREWS AND TAILS FOR ALL METAL ELECTRIC RECEPTICAL BOXES.