Permit: T16CM07630

Parcel: 205942500

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T16CM07630

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/15/2016 MECHANICAL - INTERMEDIATE Approved
12/14/2016 MECHANICAL - INTERMEDIATE Denied 4th inspection; again min 1" clearance req for B-vent,
plumb and align joints dn strs
12/13/2016 MECHANICAL - INTERMEDIATE Denied Work covered prior to approval; 109.3
Exspose B vent dn stairsand upstairs. Provie a ladder to check dwv for test.
12/09/2016 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
12/09/2016 MECHANICAL - INTERMEDIATE Denied PVC joints require the use of PVC PRIMER per code.
Support line set tubing close to appliance connection and in wall.
Support line set tubing above ceiling, protect tubing from safety plate.
Repair top plate; over notched.
Type B vent may not offset more than 60 from vert. requires 1" clearance from combustibles
Support exhaust duct
12/08/2016 MECHANICAL - INTERMEDIATE Denied PVC joints require the use of PVC PRIMER per code.
Support line set tubing close to appliance connection and in wall.
Support line set tubing above ceiling, protect tubing from safety plate.
Repair top plate; over notched.
Seal torn insulation.
Correct the slope and supports of condensate drains.
Type B vent may not offset more than 60 from vert. requires 1" clearance from combustibles
Support exhaust duct
12/07/2016 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*