Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T16CM07500
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/29/2017 | FIRE - FINAL | Approved | Approved. Separate hood permit still open, see notes under that permit. Also, They've been ordered to obtain Assembly operational permit. | |
12/14/2016 | FIRE - FINAL | Denied | 1) Need annual fire alarm inspection report. 2) Extinguishers need servicing. Mount one in main lobby. 4) Need current hood report. Tag from '13 5) Hood problems. Coverage not correct. Appliances moved or orignal appliances replaced. Cintas to do work. 6) Add suite numbers to front and rear doors. FINAL WILL NOT BE APPROVED WITHOUT HOOD REPORT AND HOOD PROBLEMS RESOLVED. COOKING SHALL BE PROHIBITED. |
|
11/30/2016 | FIRE - FINAL | Denied | 1) Missing escutcheons. 2) EM lights not working. 3) Extinguishers need servicing. 4) Need current hood report. Tag from '13 5) Hood problems. Coverage not correct. Appliances moved or orignal appliances replaced. Need to verify with original plans. 6) Add suite numbers to front and rear doors. FINAL WILL NOT BE APPROVED WITHOUT HOOD REPORT AND HOOD PROBLEMS RESOLVED. COOKING SHALL BE PROHIBITED. |