Inspection History: ENGINEERING - FINAL

Date Description Inspector Results Comments
10/09/2017 ENGINEERING - FINAL Approved
08/24/2017 ENGINEERING - FINAL Denied 1) DUE TO THE FACT THAT NO SITE/GRADING/LANDSCAPING OR STORM WATER INSPECTIONS WERE CALLED IN DURING CONSTRUCTION - PROVIDE A CERTIFICATION STATEMENT FROM THE ENGINEER OF RECORD STATING THAT SITE/GRADING WAS IN CONFORMANCE WITH THE APPROVED GRADING PLAN.
2) PROVIDE SHORT TERM BIKE PARKING PER PLAN.
3) PROVIDE EXTRUDED CURB PER NOTE#24, PAGE C1.0
4) PROVIDE PARKING BUMPERS PER NOTE#28, PG C1.0
5) PROVIDE LOADING ZONE PER NOTE#21, PG C1.0
6) PROVIDE LONG TERM BIKE PARKING PER NOTE#37, PG C1.0
7) PROVIDE SET BACK FOR PARKING ALONG NORTH WALL PER NOTE#4, PG C1.0
8) APPROVED PLANS DO NOT SHOW A VALLEY GUTTER, BUT SHOW A DETAIL FOR ONE.
08/03/2017 ENGINEERING - FINAL Denied 1) NO CONTACT, NO ACCESS.
2) NO SITE INSPECTIONS CALLED IN THROUGHOUT CONSTRUCTION.
3) FINAL PERMIT # DP16-0171