Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2016 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/21/2016 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
| 10/21/2016 | ELECTRIC - FINAL | Denied | water and gas are bonded to each other but not to grounding system, bonding needs to continue to panel. a re-fee is being attached to this permit. |
|
| 10/18/2016 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
| 10/18/2016 | ELECTRIC - FINAL | Denied | work not being done,a re-fee is being attached to this permit | |
| 10/13/2016 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/13/2016 | ELECTRIC - FINAL | Partial Approval | bonding required to gas and water |