Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2017 | MECHANICAL - INTERMEDIATE | Approved | ||
| 03/16/2017 | MECHANICAL - INTERMEDIATE | Denied | ELEC. CONDUIT NOT APPROVED FOR DRAIN PIPING. DRAIN MUST BE 3/4" I.D. PLUMBERS TAPE NOT APPROVED FOR SUPPORTING FAN COIL. SHOW HOW SECONDARY DRAIN IS PROVIDED. PROVIDE INSTALL INSTRUCTION FOR FAN COIL. PROVIDE FIRESTOPPING AT EXISTING WALL. REPAIR BROKEN CLEANOUT IN EASEMENT. |