Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2017 | FIRE - FINAL | Approved | ||
| 02/25/2017 | FIRE - FINAL | Partial Approval | fire sprinkler plans are approved for interrior only, outside is a seperate permit that was denied. Fire alarm system needs one horn strobe added back midwest section. Fire bell needs to be wired and tested. Emergency power and emergency lights came on within 5 seconds of power loss. | |
| 12/21/2016 | FIRE - FINAL | Partial Approval | j-box's in the ceiling need to be covered. 3 exit lights need to be replaced. Need to come back and check the assembly areas for the emergency exit lighting. See permit T16FC00289 for fire alarm issues. Ok to end the fire watch |
|
| 12/20/2016 | FIRE - FINAL | Partial Approval | Could not perform the fire final. Continue the fire watch. FACP needs to be monitored. | |
| 12/19/2016 | FIRE - FINAL | Partial Approval | Could not perform the fire final. Continue the fire watch. FACP needs to be monitored. | |
| 12/15/2016 | FIRE - FINAL | Partial Approval | Could not perform the fire final. Continue the fire watch. FACP needs to be monitored. | |
| 12/08/2016 | FIRE - FINAL | Partial Approval | 1) PA on sprink. Columns 4-9 & 9F-11E. 2) Alarm denied, not ready. 3) TCO approved for areas noted above. 4) Fire watch order issued to Raytheon. Fire watch shall be established to occupy with TCO. 5) Needs fire alarm final and bldg final. 6) Remove old address numbers. 7) Verify extinguishers. 8) Verify exiting hardware, exit signs, EM lighting. |
|
| 10/18/2016 | FIRE - FINAL | Partial Approval | This is inspection for sprinkler system only. OH partial approval on small section, see plans. OK to hard lid this area. |