Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2016 | ELECTRIC - RECONNECT | Approved | ||
| 09/15/2016 | ELECTRIC - RECONNECT | Denied | BREAKERS ARE NOT LABELED, 3/4" CONDUIT AT BOTTOM OF PANEL IS NOT SECURED TO THE STRUCTURE WITH AN ILLEGAL WIRE METHOD OR ROMEX DIRECT BURY TO THE SHED, WATER BOND IS MADE BUT NO GROUND RODS WITH MANAGER SAYING THAT THE WATER LINE UNDERGROUND IS PLASTIC, NO GAS BOND, NO SMOKE DETECTOR IN A BEDROOM, NO CO DETECTOR AJACENT TO A WATER HEATER LOCATED IN MAIN HALLWAY, NO GFCI IN BATHROOM, NO GFCI AT KITCHEN SINK. |