Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2017 | ELECTRIC - FINAL | Approved | ||
| 04/03/2017 | ELECTRIC - FINAL | Denied | 1. 2 wire system must be 2 prong outlets or gfi's. All units. 2. only 1 circuit for kitchen counters. Need 2. All units. 3. Unit # 8 - South kitchen counter outlet has to be within 2' of the end of the counter. 4. Arc fault all appropriate circuits per plan and code. All units. 5. Dishwasher circuits must be gfi. 6. Unit # 6 needs main disconnect and knockout plugs. 3. |
|
| 03/08/2017 | ELECTRIC - FINAL | Partial Approval | OK RES. INCR 5 METERS #5, 6, 7, 8, AND HOUSE. | |
| 03/07/2017 | ELECTRIC - FINAL | Partial Approval | PROVIDE A GROUNDING ELECTRODE SYSTEM AND WATER/GAS BOND. | |
| 02/29/2016 | ELECTRIC - FINAL | Partial Approval | Notes transferred from T16CM01079- line side only, recall for load side. |