Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T16CM06828

Parcel: 138243950


Addresses:

1715 W VALENCIA RD

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
06/28/2017 ELECTRIC - UFER Approved ECO
06/26/2017 ELECTRIC - UFER Denied SEE SERVICE ENTRANCE GROUNDING PER 2/E4 VERIFY MINIMUM 20' DEVELOPED LENGTH UFER
PROVIDE APPROVED ALTERNATIVE OPTION FROM ENGINEER OF RECORD
06/22/2017 ELECTRIC - UFER Not ready for Inspection provide ground reading (OHM) documentation