Permit: T16CM06696

Parcel: 130110640


Addresses:

1911 S HOWARD SV

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
11/07/2016 ELECTRIC - RECONNECT Approved INCR
11/04/2016 ELECTRIC - RECONNECT Approved
09/06/2016 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999
Protect conductor's at their ampacity, isolate neutral at sub-panel, protect any romex below 8 feet, provide smoke alarms thru out, provide dead front on main and sub panel, Note : w/heater t + p line undersized, no combustion air to furnace.

*
09/01/2016 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*