Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2016 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL PROVIDE DBL. WALL FLU VENT FOR THE VENT CONNECTOR TO THE FIRST OFF SET 90 FOR TH (6") CLEARANCE REQUIREMENT FOR SINGLE WALL FLU VENT. * |
|
| 10/05/2016 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- GAS PRESSURE TEST PROVIDED. 2- GAS SHUT OFF VALVES ARE OKAY. 3- GAS BOND PROVIDED. 4- NOTE: THE EXISTING WATER HEATER FLU VENT IS LOCATED UP AGAINST THE CEILING RAFTER AND WOOD BEAM. DBL. WALL FLU VENT SHALL HAVE A MINIMUM OF 1" CLEARANCE AROUND COMBUSTIONABLE MATERIAL AND A MINIMUM OF 6" CLEARANCE AROUND THE SINGLE WALL VENT CONNECTOR. 5- SHALL PROVIDE (3) SHEET METAL SCREWS PER JOINT ON THE WATER HEATER FLU VENT. * |
|
| 09/28/2016 | PLUMBING - FINAL | Not ready for Inspection | CONTRACTOR CANCELLED. |