Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T16CM06650
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/19/2017 | FIRE - FINAL | Approved | ||
05/18/2017 | FIRE - FINAL | Partial Approval | Still needs: 1) flow test (inspectors test) and main drain test. 2) correct time zone with central station. 3) FDC knox cap, show proof that it's ordered. 4) place keys in knox box. |
|
05/12/2017 | FIRE - FINAL | Partial Approval | Emergency & Exit lights OK Fire Extinguishers OK Only need: FACP Sign Fire alarm and fire sprinkler final |